Siemens machines ​

Chatter reads Siemens SINUMERIK controls (840D sl, 828D, ONE) through the OPC UA server that is built into the control. It needs no extra software on the Chatter computer.

Set up the control ​

  1. The control needs the OPC UA option ("SINUMERIK Access MyMachine /OPC UA"). It must be licensed and turned on.
  2. On the control, open Commissioning > Network > OPC UA and check that OPC UA is on. Its port is usually 4840.
  3. Give Chatter a login with read rights (SinuReadAll), or turn on anonymous access.

A SINUMERIK control allows only a few OPC UA sessions. Chatter uses one session for each machine. Do not add the same control twice.

Add the machine ​

Add the machine with the type Siemens SINUMERIK. Then, on the machine page, open Settings and set:

  • OPC UA port: usually 4840.
  • Security: None, or Sign and encrypt (Basic256Sha256).
  • OPC UA username and OPC UA password: the login from the control. Leave the username empty for an anonymous login.

The server never sends the password back, the same as the FTP password.

Sign and encrypt ​

With Sign and encrypt, the control must trust the certificate of Chatter:

  1. Save the settings in Chatter. Chatter makes its certificate and tries to connect. The control rejects the first try.
  2. On the control, open Commissioning > Network > OPC UA > Certificates. Move the Chatter certificate from Rejected to Trusted.
  3. Chatter connects at its next try.

Chatter keeps its certificate in the data folder (in opcua-pki, next to chatter.db), so the certificate stays after an update and you trust it only once. All Siemens machines use the same certificate. Chatter trusts the certificate of each control the first time it connects.

What Chatter reads ​

Chatter reads these values from channel 1 of the control, every poll, in one request:

ValueSINUMERIK variable
Run state/Channel/State/chanStatus: 0 reset (Ready), 1 active (Running), 2 interrupted
Program state/Channel/State/progStatus
Mode/Bag/State/opMode: JOG, MDA or AUTO
Program/Channel/ProgramInfo/selectedWorkPProg, shown as PART1.MPF
Parts and part goal/Channel/State/actParts and /Channel/State/reqParts
Tool/Channel/State/actTNumber and /Channel/State/actToolIdent
Spindle speed and load/Channel/Spindle/actSpeed and /Channel/Spindle/driveLoad
Feed and feed override/Channel/State/actFeedRateIpo and /Channel/State/feedRateIpoOvr

The run state must be readable. A control that does not have one of the other values leaves it empty. The control counts parts only when its part counter is set up (machine data MD27880).

On the machine page, R parameters adds R parameters to the Current job card: type 5 to read R5.

Alarms ​

The control sends its alarms as OPC UA events. When Chatter connects, it asks for the alarms that are active already. The alarm code is the SINUMERIK alarm number, for example 700209. If the control sends no alarm events, Chatter still reads the other values, and the machine page tells why the alarms are missing.

Check ​

When a machine does not connect, the machine page shows the reason:

MessageMeaning
BadUserAccessDeniedWrong username or password, or the user has no read rights
The connection cannot be establishedOPC UA is off or not licensed, or the IP address or port is wrong
BadSecurityChecksFailed or BadCertificateUntrustedThe control does not trust the Chatter certificate yet (see Sign and encrypt)
Cannot read /Channel/State/chanStatusThe control does not give the SINUMERIK variables, or the user cannot read them

The values in the table above were checked on SINUMERIK 828D controls. Other versions may give some values under other names.